Governor OPD (PFG300 OPD): worker and monitor regulators in series with sensing line by Pietro Fiorentini
Governor - USA market

Governor OPD PFG300 OPD - Regulator with Integrated Over Pressure Device, 10 psig Inlet

PFG300 OPD is a regulator from the GOVERNOR series with an integrated Over Pressure Device, CSA certified to ANSI Z21.80 / CSA 6.22 as a Class II Line Gas Pressure Regulator for inlet pressure up to 10 psig (689 mbar), with an outlet pressure range from 2″ w.c. to 14″ w.c. (5 to 35 mbar). It allows vent-limited, multi-position installation and provides positive dead-end lockup for sizes 1/2″ through 4″. It also features a double diaphragm with an integral vent limiter, an external vent limiter, and a balanced valve design for increased capacity and accuracy.

Pietro Fiorentini lists this model in its “Governors - USA only” range (CSA / ANSI certified). Contact us to confirm availability for your project.

CSA Class II Certified
Inlet 7″ w.c. to 10 psig (17 to 689 mbar)
Integrated Over Pressure Device

Technical Specifications

Performance
Inlet Pressure Range17.4 to 689 mbar (7″ w.c. to 10 psig)
Max. Inlet Pressure (non-certified applications)Up to 689 mbar (10 psig)
Downstream Pressure (Wd) (certified)5 to 35 mbar (2″ to 14″ w.c.)
Downstream Pressure (non-certified applications)Up to 293 mbar (4.25 psig)
Monitor Safety PressureNormally 70% above the working regulator pressure
Max. Emergency Inlet Exposure Pressure5.5 bar (80 psig)
Turndown500:1
Capacity (0.6 SG gas, with filter, 8″ w.c. set point, 3 to 10 psig inlet)22 to 932 m³/h (785 to 32,905 cfh), 1/2″ to 4″
Construction
Operating Temperature-40 °C to +65.5 °C (-40 °F to 150 °F)
Nominal Sizes1/2″ through 4″
ConnectionsNPT (1/2″ to 2″); ANSI 150 flanged (2-1/2″ to 4″)
StandardsANSI Z21.80 / CSA 6.22, Class II Line Gas Pressure Regulator
Gas CompatibilityNatural Gas, LPG and any non-corrosive clean gas
InstallationIndoor and outdoor (brass vent limiter removed for outdoor installation)

Applications

Residential to Large Industrial Applications
Upstream of Utility Meters
Burner Supply
Generators, Pool Heaters, High Turn-Down Boilers (High Capacity)

Key Features

Integrated Over Pressure Device

Regulator with an integrated Over Pressure Device (worker and monitor arrangement for added safety).

Monitor Keeps Outlet Below CSA Limit

If the regulating regulator fails, the monitor regulator takes over at a safety pressure normally 70% above the regulator pressure, keeping the set point below the CSA limit of 2 psig.

CSA Class II Certified

Certified to ANSI Z21.80 / CSA 6.22 Class II for outlet pressures up to 14″ w.c. and inlet pressure up to 10 psig.

Hydrogen Ready

Suitable for NG-H2 blending.

Frequently asked questions

What is the Over Pressure Device on the Governor OPD?

The Governor OPD (PFG300 OPD) has a worker and a monitor regulator in series. If the working regulator fails, the monitor takes over at a safety pressure normally 70% above the working set point, keeping the outlet below the CSA limit of 2 psig. It is certified Class II to ANSI Z21.80 / CSA 6.22.

Should I choose the Governor OPD or the Governor Dual Cut?

Both are Class II line regulators for inlet up to 10 psig with certified outlet of 2 to 14 inches w.c. and sizes from 1/2 to 4 inches. The Governor OPD accepts a lower inlet, from 7 inches w.c., and protects with a monitor. The Governor Dual Cut needs at least 3 psig inlet and protects with a fixed 1.7 psig upstream stage.

Can the Governor OPD be supplied outside North America?

Pietro Fiorentini lists the Governor OPD in its USA range, certified to CSA / ANSI standards. Contact us with your application and inlet conditions, and we will confirm availability for your project and whether the certification matches your requirements.

Need More Information?